If you’ve ever worked around transformers or generators, you’ve probably heard the term separately derived system. But a lot of electricians still get tripped up on one critical rule that comes with them.
Let’s break it down clearly.
A separately derived system is an electrical system that has no direct electrical connection to another supply. Classic examples include:
The secondary of a transformer
A generator that is not solidly tied to the utility (i.e., the neutral is switched)
In short: it’s its own independent power source.
On the load side of the system bonding jumper, the grounded conductor (neutral) can NEVER be reconnected to ground, to equipment grounding conductors, or to non-current-carrying metal parts.
Doing so creates a dangerous parallel path for normal neutral current. That is both a code violation and a real safety hazard.
This rule is clearly stated in NEC 270.30(A) (the medium-voltage grounding and bonding article in the 2026 NEC):
“Except as otherwise permitted in this article, a grounded conductor shall not be connected to normally non-current-carrying metal parts of equipment, be connected to equipment grounding conductors, or be reconnected to ground on the load side of the system bonding jumper.”
The system bonding jumper is the single point where the neutral is intentionally connected to the equipment grounding system and the metal enclosure.
Once that connection is made, the neutral must stay isolated from ground everywhere downstream. If you bond it again (for example, by installing a bonding screw in a downstream panel), you create parallel return paths. Normal neutral current will flow on equipment grounding conductors and metal parts — exactly what we are trying to prevent.
Imagine a transformer secondary:
At the transformer (or at the first disconnect), you install the system bonding jumper.
From that point forward, the neutral bus and the equipment ground bus in every panel must remain separate.
That’s it. One bonding point only.
System bonding jumper = the only place the neutral is allowed to touch ground.
Everywhere on the load side of that jumper → Neutral and ground stay isolated.
Rebonding the neutral downstream = parallel path = code violation + safety issue.
This rule has been around for a long time, but with the 2026 NEC creating a dedicated Article 270 for medium-voltage grounding and bonding, it’s worth reviewing again — especially if you work on systems over 1000 volts.
Stay sharp out there.