2026 NEC References: 230.72, 230.74–230.81
Having multiple service disconnects isn't the end of the requirements.
They also have to be properly grouped, identified, operated, and rated.
The permitted service disconnects generally have to be grouped.
Each disconnect needs identification for the load it serves.
Specific fire-pump and emergency/standby arrangements have additional requirements.
Each disconnect has to open the ungrounded conductors simultaneously.
Where the grounded conductor isn't disconnected by the service disconnect, the applicable separate terminal or bus arrangement is required.
Disconnects can be manually or power operated under the applicable conditions.
Power-operated disconnects must still be capable of being manually opened during a power failure.
The source material identifies these minimum ratings:
15A — single branch circuit
30A — up to two 2-wire circuits
100A — one-family dwelling
60A — other installations
Where multiple disconnects share the load, their combined rating has to meet the applicable minimum.
Connections to the disconnect use approved pressure connectors, clamps, or similar means.
Solder isn't the connection method.
What's the minimum service disconnect rating for a one-family dwelling?
Answer: 100 amperes.
A service disconnect has to be:
Located correctly.
Grouped correctly.
Identified correctly.
Rated correctly.
Capable of proper operation.
➡️ Next Quick Hit: Supply-side equipment and overcurrent protection.