SLIDE 1
🔥 LET'S PUT IT ALL TOGETHER
You have:
3/4" EMT
12 × #12 THHN
Question:
DO THEY FIT?
SLIDE 2 — FIND THE RACEWAY AREA
📚 Chapter 9, Table 4
3/4" EMT:
0.533 in² total internal area
3+ conductors → 40%
So:
0.533 × 0.40
= 0.2132 in²
SLIDE 3 — FIND CONDUCTOR AREA
#12 THHN:
0.0133 in²
12 conductors:
0.0133 × 12
= 0.1596 in²
Now compare:
0.1596 < 0.2132
🔥 THE CONDUCTORS FIT
SLIDE 4 — FINAL EXAM QUESTION
3/4" EMT
12 × #12 THHN
40% fill limit
Does it pass conduit fill?
A️⃣ YES
B️⃣ NO
🔥 YES
But remember:
FILL IS ONLY ONE PART OF THE NEC CHECK.
FOLLOW FOR MORE DAILY NEC STUDY NOTES ⚡
“DON'T JUST MEMORIZE THE NUMBER — LEARN WHERE IT COMES FROM. OPEN THE NEC. DO THE MATH. VERIFY IT. ⚡”