2026 NEC References: 230.30, 230.31, 230.32, 230.33
When the service goes underground, Article 230 gives you its own requirements for insulation, wiring methods, sizing, and protection.
Underground service conductors generally need insulation appropriate for their voltage.
Specific exceptions permit certain bare copper and aluminum/copper-clad aluminum conductors under the conditions established by the Code.
Approved methods include specific raceways and cable types such as:
RMC
IMC
PVC
RTRC
HDPE
NUCC
Type IGS
Type USE
Certain MV/MC/MI/TC-ER cables
The specific application and listing requirements matter.
General minimum:
8 AWG copper
6 AWG aluminum
Certain single limited-load branch-circuit applications allow smaller conductors under the specified conditions.
What's the minimum aluminum conductor size for underground service conductors serving only a single limited-load branch circuit?
Answer: 10 AWG aluminum or copper-clad aluminum.
The corresponding copper minimum is 12 AWG copper.
Underground doesn't mean "anything rated for underground."
Wiring method + insulation + conductor size + physical protection all have to line up.
➡️ Next Quick Hit: How many sets of service-entrance conductors can you run?