2026 NEC References: 230.26, 230.27, 230.28, 230.29
Now we're getting to where the overhead service conductors actually attach to the building.
The attachment point must satisfy the applicable clearance requirements.
It also cannot be lower than:
10 ft above finished grade.
Multiconductor cable needs fittings identified for service use.
Open conductors require appropriate fittings or suitable noncombustible, nonabsorbent insulators securely mounted to the structure.
A service mast is there for the service conductors.
Other communication or utility conductors can't simply be attached to the mast.
The mast also needs enough strength — or appropriate bracing/guying — to withstand the mechanical forces involved.
Where service conductors cross over a roof, substantial support is required.
Where applicable, metal supports on a grounded system have bonding requirements.
What's the minimum height above grade for the point of attachment of overhead service conductors?
Answer: 10 ft (3.0 m).
The service drop doesn't just magically attach to the building.
Attachment point + fitting + mast/support + clearance all matter.