⚡ NEC Quick Hit: Conductor Properties & DC Resistance (Table 8) ⚡
Doing voltage drop calculations? You live and die by Chapter 9 Table 8. Let's break down DC resistance at $75^\circ\text{C}$ for copper and aluminum conductors from #14 up to heavy feeders! 👇
SLIDE 2 (COMMON BUILDING WIRE SIZES: #14 to #2)
DC Resistance ($\Omega$ per 1,000 ft at $75^\circ\text{C}$):
#14 Solid Copper: 3.07 $\Omega$ / kFT (Aluminum: 5.06)
#12 Solid Copper: 1.93 $\Omega$ / kFT (Aluminum: 3.18)
#10 Solid Copper: 1.21 $\Omega$ / kFT (Aluminum: 2.00)
#8 Stranded Copper: 0.778 $\Omega$ / kFT (Aluminum: 1.28)
#2 Stranded Copper: 0.194 $\Omega$ / kFT (Aluminum: 0.319)
SLIDE 3 (HEAVY FEEDER SIZES: 1/0 to 500 kcmil)
Feeder DC Resistance ($\Omega$ per 1,000 ft at $75^\circ\text{C}$):
1/0 Stranded Copper: 0.122 $\Omega$ / kFT (Aluminum: 0.201)
4/0 Stranded Copper: 0.0608 $\Omega$ / kFT (Aluminum: 0.100)
250 kcmil Copper: 0.0515 $\Omega$ / kFT (Aluminum: 0.0847)
500 kcmil Copper: 0.0258 $\Omega$ / kFT (Aluminum: 0.0424)
SLIDE 4 (FIELD TAKEAWAY & WRAP-UP)
💡 Apprentice Pro-Tip: Notice how aluminum resistance is consistently higher than copper for the same gauge size? That's why aluminum conductors generally require a size bump up when you're calculating long runs and mitigating voltage drop!
💬 Save this post for your next voltage drop exam question or field calculation!