SLIDE 1 (HOOK / COVER)
⚡ NEC Quick Hit: Cord Repairs, Strain Relief & Grounding (Part 4) ⚡
Hard-service cord splicing rules, strain relief, and green grounding identification—let's finish Article 400! 👇
SLIDE 2 (SPLICES AND REPAIRS)
Keeping Cords Continuous:
Initial Installation: Flexible cords must be used in continuous lengths without splices or taps when initially installed.
Repair Permissions: Repair of hard-service and junior hard-service cords 14 AWG and larger is permitted if spliced per Section 110.14(B) and the completed splice retains the original insulation, outer sheath properties, and usage characteristics.
No Reinstallation of Splices: Once a repaired cord is removed, that same in-line spliced cord cannot be reinstalled at a new location.
SLIDE 3 (STRAIN RELIEF, PROTECTION & GROUNDING IDENTIFICATION)
Physical Safety and Conductor Marking:
Pull Elimination: Cords must be connected to devices and fittings so that tension is not transmitted to joints or terminals (using strain relief, knots, or tape).
Physical Protection: Cords passing through holes in covers or outlet boxes must be protected by bushings or fittings.
Grounding Identification: Equipment grounding conductors must have a continuous green color or green with yellow stripes. Grounded circuit conductors are identified via colored braids, white/gray insulation, tinned strands, or exterior surface ridges/stripes.
SLIDE 4 (WRAP-UP) 💡 Apprentice Pro-Tip:
Never rely on terminal screws to hold the physical pulling weight of a cord—always ensure proper strain-relief fittings are installed to eliminate tension on internal electrical connections!
💬 Save this post for your final code review on Flexible Cords!
🔗 More code breakdowns and study tools at www.JoshTheSparky.com