2026 NEC References: 230.41, 230.42, 230.43, 230.44
Service-entrance conductors have specific rules for insulation, sizing, and approved wiring methods.
The conductors need to be sized for the calculated load.
The source material's key calculation concept is:
Noncontinuous load + 125% of continuous load
Certain exceptions allow 100% sizing when the applicable equipment or overcurrent protection is listed for 100% continuous operation, along with other specified situations.
Article 230 permits numerous wiring methods under their applicable conditions, including:
Open wiring
RMC
IMC
EMT
ENT
SE cable
Wireways
Busways
Auxiliary gutters
PVC
Cablebus
MC
MI
FMC/LFMC under limited conditions
LFNC
HDPE
NUCC
RTRC
TC-ER identified for service use
Cable trays can also be used for certain service-entrance conductors under specified conditions.
What's the maximum length allowed for FMC or LFMC used as a service-entrance wiring method?
Answer: 6 ft (1.8 m).
A supply-side bonding jumper is also required alongside it under the applicable rule.
Don't just ask:
"Can I use this wiring method?"
Ask:
"Can I use this wiring method for THIS service application, under THESE conditions?"