⚡ NEC 2026 Quick Hit: Article 342 - Intermediate Metal Conduit (IMC) ⚡
Running IMC on the job? Because IMC has thinner walls than Rigid (RMC) but thicker walls than EMT, its internal area gives you a bit more room to breathe.
Here is your Chapter 9 Table breakdown from 1/2" to 6" 👇
Slide 2: Common Small Sizes (1/2" - 1")
Small IMC Trade Sizes:
1/2" (Metric 16)
100% Total Area: 0.342 in²
Over 2 Wires (40%): 0.137 in²
ID: 0.660 in.
3/4" (Metric 21)
100% Total Area: 0.586 in²
Over 2 Wires (40%): 0.235 in²
ID: 0.864 in.
1" (Metric 27)
100% Total Area: 0.959 in²
Over 2 Wires (40%): 0.384 in²
ID: 1.105 in.
Slide 3: Mid & Large Sizes (1-1/4" - 4")
Medium to Large IMC Sizes (40% Fill Limit):
1-1/4": 0.659 in² (100% = 1.647 in² | ID: 1.448 in.)
1-1/2": 0.890 in² (100% = 2.225 in² | ID: 1.683 in.)
2": 1.452 in² (100% = 3.630 in² | ID: 2.150 in.)
3": 3.169 in² (100% = 7.922 in² | ID: 3.176 in.)
4": 5.452 in² (100% = 13.631 in² | ID: 4.166 in.)
Slide 4: Field Takeaway & Wrap-Up
💡 Apprentice Pro-Tip:
Notice there's no 3/8" trade size for IMC (starts at 1/2").
Also, compare IMC's 1/2" 40% fill (0.137 in²) to EMT's 1/2" 40% fill (0.122 in²)—that extra space in IMC can make a huge difference when you're pulling tight wire combinations!
💬 Save this post for your next pipe calculation or feeder run! 🔗 More code breakdowns & study tools at www.JoshTheSparky.com