Welcome to Article 215 — Feeders!
In Article 210, we covered branch circuits. Now we're moving one step upstream to Article 215, where we focus on feeders — the conductors supplying power to the branch-circuit overcurrent devices.
In this first episode, we'll cover the scope of Article 215 and the minimum rating and sizing requirements for feeders.
Article 215 covers the installation, overcurrent protection, minimum size, and ampacity requirements for feeders operating at:
1000 volts AC or less
1500 volts DC or less
For systems exceeding these voltage limits, Article 266 applies.
A feeder is the conductor run between the service equipment, or another power source, and the final branch-circuit overcurrent device.
Think of it as the trunk line that carries power before it splits into individual branch circuits.
Feeder sizing involves many of the same continuous-load calculations covered in Article 210.
For a feeder supplying a combination of continuous and noncontinuous loads, the minimum ampacity is calculated using:
Noncontinuous load + 125% of continuous load
This is the general calculation unless a qualifying 100%-rated assembly or another applicable provision allows different treatment.
A feeder segment connected at both ends with separately installed pressure connectors may be sized based on the maximum actual load without the additional 125% continuous-load factor, as described in the source material.
When the grounded conductor is not connected to an overcurrent device, it does not require the 125% continuous-load factor under the provision described here. It is sized at 100% of the load.
The feeder's grounded conductor also cannot be smaller than the size required by 250.122 for an equipment grounding conductor of the same circuit.
When a feeder carries the full load of service conductors rated 55 amperes or less, the feeder ampacity cannot be less than the ampacity of those service conductors.
Question: A feeder supplies a combination of continuous and noncontinuous loads. What is the minimum ampacity formula, absent a 100%-rated assembly?
A) Continuous load only
B) Noncontinuous load + 125% of continuous load
C) 80% of total load
D) Noncontinuous load + 100% of continuous load
The formula is noncontinuous load plus 125% of continuous load, as described in 215.4(A)(1).
This is the same general continuous-load calculation concept covered in Article 210, now applied to feeders.
Feeders are the conductors supplying branch-circuit overcurrent devices. Understanding their minimum ampacity requirements is essential when moving from branch circuits to the larger distribution system.
Follow for more daily quick-hit study notes!
📚 Next: Episode 2 — Overcurrent Protection, Equipment Grounding, Tapped Conductors & Feeder GFCI.
Study note: This is an educational overview. Consult the applicable 2026 NEC text and local requirements for complete installation rules.