Slide 2 — Locking, indicating, position & identification
(D) Lockable open per 110.25 (fused cutouts are exempt from this).
(E) Must clearly show open/off vs. closed/on.
(F) Vertically operated handles: "up" = "on" (exception for multi-position switches like double-throw).
(G) If a building has any combination of feeders/branch circuits/services passing through or supplying it, a permanent plaque/directory at each disconnect location must identify everything else supplying or passing through, and the area each one serves.
Slide 3 — Operation, grounded conductor & isolating switches
(H) Manually operable (handle-equipped switch/breaker) OR power-operable (as long as it can be opened by hand during a power failure).
(I) If the disconnect doesn't disconnect the grounded conductor itself, another means (like a pressure-connector terminal/bus) must be provided at that location — multisection switchgear can have this in any marked section.
(J) If the disconnect lacks visible break contacts, a visible-break isolating switch (meeting specific 268.70(E) sub-requirements and 495.22) is required on its supply side — exempt only for removable truck panels/switchgear units that auto-disconnect when removed.
Slide 4 — Quiz + CTA Q: "For a vertically operated disconnect handle, which position indicates 'on' (absent a multi-position exception)?" A) Down B) Up C) Horizontal D) It doesn't matter
✅ Answer: B — 267.31(F): "up" = "on" for vertically operated handles.